DATA CENTER Tier III++ 
Main Structural Features
  • Steel structure and pre-cast concrete panels, aluminium glazing to offices.
  • Typical floor loading of 9kN/m². 20 kN/m² in somespecific areas.
  • Slab to slab height of 3.70m.
  • Raised floors with anti-static tiles with a height of between 600mm to 800mm. Clear height of between 3.20m - 2.80m.
  • Column spacing: 9.84m.

Redundant Power

  • N+N redundancy on power supply.
  • Mains power supplied via 2 x 15kV incomers.
  • Diverse A&B supply, distributed via 15kV main.
  • Up to 1000 w/m² of power available on each floor.
  • Backed up by 15kV diesel generators in N+1 configuration.
  • On-site diesel tanks (2 x 50,000 litres) support 24 hours at full capacity with 8 hour, 24x7 fuel delivery callout contract in place.

Cooling and Environment

  • N+1 redundancy on cooling system.
  • Temperature and humidity in technical space to industry accepted standards and maintained within energy efficient parameters.
  • Hydraulic redundancy.
  • Computer room air conditioning units (CRACs) in technical area backed up by 15kV diesel generators in N+1 configuration.

 

Fire Detection and Suppression
  • Analogue fire detection system in all areas (smoke and heat) with manual break-glass units.
  • VESDA early warning system.
  • State of the art suppression systems in technical areas.
  • Wet risers and hose reels to all floors from site dedicated fire pump room and tanks.
  • CO² suppression systems in substation transformers.

Building Management Systems
  • Dedicated 24x7 facilities management team.
  • Full power monitoring system.
  • Asset management system.
  • BMS system monitors M&E operation within data centre to:
    - ensure stability of the environment.
    - monitor key electrical and mechanical systems.
    - enable interface between key systems.
    - provide data gathering.

Telecommunications

  • Carrier Neutral.
  • Access to multiple telecommunications providers located within the data centre.
  • Diverse cable entry points with a combination of 160mm and 32mm sub ducts.
  • Basket trays to all data risers - fully access controlled.
  • Multiple connection points to each area.
  • Roof space availability for satellite and antenna equipment.


Security

  • Premises Controllers manage data centre security 24x7.
  • Access control using proximity card readers.
  • Intruder alarms to all areas.
  • Multiple CCTV cameras (interior and exterior).
  • Gate controlled vehicle access.
  • Secure managed delivery and loading areas.
  • Secure car park.