Main Structural Features
- Steel structure and pre-cast concrete panels, aluminium glazing to offices.
- Typical floor loading of 9kN/m². 20 kN/m² in somespecific areas.
- Slab to slab height of 3.70m.
- Raised floors with anti-static tiles with a height of between 600mm to 800mm. Clear height of between 3.20m - 2.80m.
- Column spacing: 9.84m.

Redundant Power
- N+N redundancy on power supply.
- Mains power supplied via 2 x 15kV incomers.
- Diverse A&B supply, distributed via 15kV main.
- Up to 1000 w/m² of power available on each floor.
- Backed up by 15kV diesel generators in N+1 configuration.
- On-site diesel tanks (2 x 50,000 litres) support 24 hours at full capacity with 8 hour, 24x7 fuel delivery callout contract in place.

Cooling and Environment
- N+1 redundancy on cooling system.
- Temperature and humidity in technical space to industry accepted standards and maintained within energy efficient parameters.
- Hydraulic redundancy.
- Computer room air conditioning units (CRACs) in technical area backed up by 15kV diesel generators in N+1 configuration.

|
Fire Detection and Suppression
- Analogue fire detection system in all areas (smoke and heat) with manual break-glass units.
- VESDA early warning system.
- State of the art suppression systems in technical areas.
- Wet risers and hose reels to all floors from site dedicated fire pump room and tanks.
- CO² suppression systems in substation transformers.
Building Management Systems
- Dedicated 24x7 facilities management team.
- Full power monitoring system.
- Asset management system.
- BMS system monitors M&E operation within data centre to:
- ensure stability of the environment.
- monitor key electrical and mechanical systems.
- enable interface between key systems.
- provide data gathering.
Telecommunications
- Carrier Neutral.
- Access to multiple telecommunications providers located within the data centre.
- Diverse cable entry points with a combination of 160mm and 32mm sub ducts.
- Basket trays to all data risers - fully access controlled.
- Multiple connection points to each area.
- Roof space availability for satellite and antenna equipment.

Security
- Premises Controllers manage data centre security 24x7.
- Access control using proximity card readers.
- Intruder alarms to all areas.
- Multiple CCTV cameras (interior and exterior).
- Gate controlled vehicle access.
- Secure managed delivery and loading areas.
- Secure car park.

|